Phase Balancing
 

Application Overview:

 

Phase imbalance is calculated from line flows resulting from the Power Flow application.  

 

Phase balancing will run for multiple circuits.  

 

The Phase Balancing application recommends phase movements of single and two-phase laterals for all user selected circuits, making use of all time points selected for analysis.

 

 

Application Run / Results:

See Running DEW Applications for general details on running an application, selecting and displaying output variables.  

 

The user may set limitations on laterals where re-phasing is allowed.  See Phase Balancing Setup for more details.   

 

The Phase Balancing application first establishes a baseline reference by evaluating the maximum phase imbalance at the start of circuit (or grounded transformers) and within the circuit over all time points specified for analysis.

 

Phase Balancing locates all laterals in the circuit, determines the total flow through each, and disconnects them from the rest of the circuit so that only the three phase portion of the circuit (the spine) is connected to the start of circuit component.  

  1. Laterals directly connected to the spine are reconnected one at a time in order of most to least loaded.  

  2. All remaining laterals (single-phase laterals connected to two-phase laterals) are reconnected from most to least loaded.  

  3. Each reconnection evaluates all possible re-phasing options and selects that which maintains the minimum imbalance at the start of circuit component.

Note!

   Ungrounded laterals are not re-phased.  The flow on these laterals is added directly to the lateral's feeder path component, so the load is realized at either the start of circuit component or on a feeder path lateral.  
   Also, phase imbalance is not performed on ungrounded start of circuit components.  For an ungrounded circuit, Phase Balancing will balance at all existing three phase grounded transformers.

 

Two output formats are available from the Phase Balancing application.  The user can generate the Phase Balancing Report, as well as cycle the displayed network through the output variables selected from the Analysis / Setup for Results Display menu.

 

 

Available Output Variables:

For general details on running an application, selecting and displaying output variables, see Running DEW Applications.  The output variables available for display from the Flicker Analysis application are described in the following table.

 

Variable

 

Description

PhMoves

-

Phase Movement Logic

Three dimension array where the 1st, 2nd, and 3rd positions correspond to Phase A, B, and C, respectively.  
Each position indicates to which phase the original phase moved.  0 -> A, 1 -> B, 2 -> C,
-1 means that the indicated phase was not originally present.

EXAMPLE:

PhMoves = [ 0 2 -1 ] indicates that Phase A did not move, Phase B moved to Phase C, and Phase C was not present.

WstDevBf

-

Worst Deviations in phase currents Before phase balancing

WstDevAf

-

Worst Deviations in phase currents After phase balancing

ChgInDev

-

Percent Change in Worst Deviations

LsMvPlot

-

Decrease in Total Loss versus Phase Moves plot