|
Note! |
The Capacitor Design application must be run with the Interactive Apps option selected (from GUI Options dialog). Otherwise, a program error occurs, generating a message to check user options. |
See Capacitor Design Setup for more details on user input options for this application. Available Output Variables for the application are described in the final section of this topic.
The Capacitor Design application models improvements in circuit performance by evaluating new capacitor placement at various locations throughout the circuit, one location at a time. The application only analyzes the first circuit selected for analysis. If more than one circuit has been selected for analysis, Capacitor Design ignores all other circuits selected after the first. If more than one time point is selected, the results apply to the earliest time point selected. If no time points are selected, Capacitor Design runs for the first time point. A design may be created by first running the application for the minimum load condition to design fixed units, and then running again for the peak load condition to design switched units.
Three types of capacitor locations are defined for the Capacitor Design application:
"Existing
Locations" are defined as those locations in the circuit where
capacitors existed before initializing the current run of the Capacitor
Design application. The user can limit the evaluation
to consider only locations where capacitors already exist. An
existing location becomes a test location if additional test units (new
capacitors) are added there for evaluation.
"Test
Locations" are defined as those locations where new capacitors
are being evaluated by the application. When run
over an entire circuit, the application may produce results for many test
locations. Improvements in voltage, power factor,
and overall circuit losses are evaluated. Some
locations will provide a greater improvement in voltage, while others
will provide a greater improvement in circuit losses. For
each location, the voltage and power factor improvements are evaluated
at the test location and also at the substation.
"Installed Locations," are defined as those locations where the user has confirmed the addition of evaluation test units into the circuit for the remainder of the evaluation. The application then incorporates results from the installed capacitors into further evaluations of other test locations. When an installed location is created, all units present at that location (i.e. both existing and test units) become installed units. Additional test units may subsequently be added to an installed location. As with existing locations, locations having both installed units and test units fall into both locational categories. Installed locations are only defined for the current run of the application.
See Running DEW Applications for general details on running an application, selecting and displaying output variables.
Interactive Run/Results:
The Capacitor Design application must be run in the interactive mode, i.e. with the Interactive Apps option selected.
If the application does not find any locations for adding capacitors that meet the specified setup criteria, then a dialog appears to allow user either to place capacitors manually or to end current run of application.
When the application finds locations for capacitor placement (or user chooses to continue with manual placement), the Command Center dialog opens, listing the results for each recommended location.

View
Test Locations/Results:
Test Locations:
List box contains all test locations, with
the current test location highlighted in the list, as well as centered
and highlighted in the drawing window.
[Test Results]
Opens a dialog presenting the user with the
Capacitor Design Test Results
for the highlighted Test Location.
|
|
|
The Capacitor Design Test Results summarize the results for selected location. [Close] - closes Test Results dialog and returns user to Command Center dialog. [Next Spot] - displays results for the next location in the (Command Center) list. |
[PFlow View]
Allows user to view power flow results for
an individual component, which is selected by mouse (pointer finger).
Once picked, the user is presented with the Capacitor
Design Component Pflow Viewer
dialog.
|
|
Current Installation Site - displays the geographical coordinates, unit ratings, and the number of units corresponding to the current (added units) installation site set in the location list. This test location is highlighted with a blue circle on the circuit diagram. Current Results Site - displays the geographical coordinates of the component where the power flow results were determined. This results site is highlighted with a red circled on the circuit diagram. Results (by phase) - Text boxes display values of the selected Power Flow output variable for the selected test location. For "Through" variables (e.g. current, power flow), the boxes give the flow values for each respective phase (A, B, C). For "Across" variables (e.g. voltages), the indicated values depend on circuit configuration, indicating individual (A, B, C) phase voltages for sections having a return path (i.e. neutral, earth, or both), or indicating phase-to-phase voltages (AB, BC, CA) for delta connected sections. Output from Power Flow - provides drop down selection of the Power Flow variable, whose results are indicated. Note: Results are shown for selected variable at the Current Results Site, with or without capacitors (i.e. test units) installed at the Current Installation Site. [Pick Cmp] - allows user to select (with pointer finger) a new location for the Results Site, where Results for the selected Output from Power Flow are applicable. [Close] - closes the Power Flow Viewer dialog
and returns the user to the Command Center dialog. |
[Next Spot]
Steps highlighted selection in list to the next test location and pans the highlighted component to center of drawing window.
Modify
Test Locations/Quantities (if needed):
[Add Test Units]
Allows user to add or modify capacitors at desired test location, which is selected with mouse (pointer finger) and may or may not be a recommended location. Once picked, the user is presented with the Add Units to this Location dialog.
|
Location (X,Y) - indicates the location selected for adding units Fixed Units - indicates fixed units that have already been added to the location during active run of application. Test Units - displays the number of recommended units (when applicable) to be added to the current test location. Add [___] - allows user to increase/decrease units to be added at location by entering positive/negative incremental value. [Update] - updates the test unit quantity by added (+) or removed (-) value entered, provided that a removal does not result in a negative number of test and fixed units at the location. [Continue] - returns user to Command Center dialog, accepting any test unit input or updates. [Cancel] - returns user to Command Center dialog, without accepting the test unit input or updates. |
Create
Installed Locations:
[Fix and Run]
Installs the units for the selected test location and drives application to reevaluate the circuit for new test locations based on inclusion of all previously installed units. Installed units will remain installed for duration of the current run of application.
Review
Installation Results:
[Installed List]
Presents the user with the Installed Location List
dialog, which lists all of the locations where capacitors have been added
during current run, via Fix
and Run command, and pans the highlighted location to center of
drawing window.
|
|
|
Shown above, the [Installed List] command was selected after choosing [Fix and Run] to install the units that gave the most improvement in circuit performance, i.e. the 5 Units/Phase that were originally listed as test location 1 of 3, with (x,y) coordinates of (-25,0). |
[Report]
Generates a text file output that contains
information about all test units and installed units. Multiple
reports may be generated in a single session. (See Capacitor Design Sample Report)
[Plot]
Presents the user with the Choose Plot Type
dialog, which allows the user to create plots of the selected output variable
versus test location. (See Capacitor Design Sample Plot)
Note: Plots cannot be generated when there is only one test location.
[Exit]
Closes the Command Center dialog and terminates the current analysis run.
For general details on running an application, selecting and displaying output variables, see Running DEW Applications. The output variables available for display from the Capacitor Design application are described in the following table. For outputs that apply to line/cable sections, the outputs are available for all phases present. Outputs that apply to circuits represent the loading associated with all three phases. Interactive outputs to the circuit schematic are available only when the application is running in the Interactive Mode.
|
Variable |
- |
Description |
|
NumUnits |
- |
Number of units that will be evaluated |
|
PrRedLs |
- |
Percent Reduction in Circuit Power (kW) Loss |
|
PrKvlnc |
- |
Percent Increase in Voltage (kV) |
|
PrPFInc |
- |
Percent Increase in Power Factor (at Test Location) |
|
PrPFSInc |
- |
Percent Increase in Source Power Factor |
|
Losses |
- |
Circuit Power (kW) Loss, With added Capacitors |
|
KVWith |
- |
Voltage Magnitude (kV), With added Capacitors |
|
PFWith |
- |
Power Factor (at Test Location) with added Capacitors |
|
SrWith |
- |
Source Power Factor, with added Capacitors |